Free Airflow Calculator • Room ACH & Tonnage Cross-Check HVAC CFM & Air Changes per Hour (ACH) Calculator
Compute room airflow (CFM) from dimensions and ACH, cross-check 400 CFM/ton cooling airflow, and estimate 6-inch branch counts.
Typical US Room ACH & CFM Reference Table
Nominal round metal and fully extended flex duct diameters below strictly satisfy
≤ 0.08 in. wg per 100 ft using
ASHRAE 2025 Chapter 21
wall roughness values (ε = 0.0003 ft steel; ε = 0.003 ft extended flex).
Sample Room CFM & Single-Duct Sizes (at 0.08 in. wg) | Room Type | Sample Dimensions | Target ACH | Volume (ft³) | Required CFM | Metal Round Ø | Flex Round Ø |
| Primary Bedroom | 14 × 16 × 8 ft | 5 | 1,792 | 149 CFM | 8" | 8" |
| Living / Great Room | 20 × 18 × 9 ft | 6 | 3,240 | 324 CFM | 10" | 10" |
| Home Office | 12 × 12 × 8 ft | 6 | 1,152 | 115 CFM | 7" | 7" |
| Bathroom Exhaust | 8 × 10 × 8 ft | 8 | 640 | 85 CFM | 6" | 6" |
| Residential Kitchen | 14 × 12 × 8 ft | 12 | 1,344 | 269 CFM | 9" | 10" |
| Workshop / Garage | 22 × 20 × 9 ft | 10 | 3,960 | 660 CFM | 14" | 14" |
ACH Formula & Ventilation Code Boundaries
- ASHRAE 62.2 Whole-Building Fresh Air: Outdoor ventilation rates under
EPA / ASHRAE 62.2 residential ventilation standards
follow
0.03 × sq ft + 7.5 × (bedrooms + 1), which is much lower
than room-level heating/cooling recirculation ACH.
- Branch Count Rule (6" Galvanized @ 0.08 in. wg): Supply register counts
divide required CFM by the exact Darcy-Weisbach 6-inch metal branch ceiling
(
96.93 CFM at ε = 0.0003 ft and 0.08 in. wg/100 ft) and round
up via ceil(CFM / 96.93). If you run fully extended 6" flex
duct instead (ε = 0.003 ft, 85.4 CFM max per branch at 0.08 in. wg), either add an extra
register or step branch runs up to 7" or 8" round flex.
- Room ACH vs. Load-Based Supply CFM: High-ceiling rooms or west-facing
sunrooms often need more cooling airflow than a flat 5–6 ACH estimate predicts, while tight
modern bedrooms can need less. Pair this ACH check with our Whole-House & Room BTU Calculator before ordering grilles
or cutting boot openings.
- Single-Duct Ceiling (15,000 CFM): Any room combination exceeding
15,000 CFM automatically switches to a Multi-Trunk requirement so large warehouse or
high-ACH calculations never output an undersized single duct.
HVAC CFM & ACH FAQ
How many CFM per ton does a US residential air conditioner require?
Standard US split AC systems require 400 CFM per cooling ton (12,000 BTU/hr). In high-humidity Gulf Coast climates, technicians often tune blower airflow down to 350–375 CFM/ton to pull more latent moisture out of the air; in arid Southwest climates, 425–450 CFM/ton improves sensible cooling capacity.
What is the difference between ACH ventilation CFM and cooling load CFM?
Air Changes per Hour (ACH) calculates how many times the entire room air volume is replaced every 60 minutes (ideal for exhaust fans, workshops, and quick circulation checks). Cooling CFM uses sensible heat gain divided by 1.08 × supply-to-return ΔT, which varies heavily with window glass and attic insulation.
How many 6-inch supply registers do I need for 300 CFM?
At 0.08 in. wg per 100 ft in smooth galvanized metal (ε = 0.0003 ft), a single 6-inch branch delivers up to 96.9 CFM quietly (~494 FPM). Delivering a full 300 CFM strictly at 0.08 in. wg therefore requires either four 6-inch branches (~75 CFM each), three 6-inch branches at a slightly higher ~0.085 in. wg friction rate, or two 8-inch branches with properly sized floor or ceiling registers.
Why does the calculator flag Multi-Trunk above 15,000 CFM?
Single-duct residential and light-commercial equal-friction sizing tops out around 15,000 CFM (where even a 48–50 inch duct runs over 1,100 FPM). Large warehouses or high-ACH industrial halls exceeding 15,000 CFM require multiple parallel air handlers or split commercial trunk zones engineered for static pressure balance.