ASHRAE Equal-Friction Duct Sizing Chart (4"–24")

Compare 4"–24" round diameters, Huebscher rectangular equivalents, CFM capacity at 0.06–0.12 in. wg, and FPM velocity across materials.

Friction Rate (in. wg / 100 ft)
Duct Wall Material
CFM

Showing Galvanized Sheet Metal capacity at 0.08 in. wg / 100 ft. Enter a target CFM to highlight the smallest compliant round duct automatically.

ASHRAE Equal-Friction Duct Capacity & Rectangular Equivalents (4"–24")
Round Ø Area (ft²) Max CFM @ 0.08 CFM @ 0.08 CFM @ 0.10 Velocity (FPM) Noise Zone Rect (~1.5:1) Rect (~2.5:1)
4" Round 0.087 32 32 37 372 FPM Quiet 4×4" 4×4"
5" Round 0.136 59 59 67 435 FPM Quiet 6×4" 6×4"
6" Round 0.196 97 97 110 494 FPM Quiet 8×4" 8×4"
7" Round 0.267 147 147 166 549 FPM Quiet 8×6" 12×4"
8" Round 0.349 210 210 238 603 FPM Quiet 10×6" 10×6"
9" Round 0.442 289 289 327 654 FPM Quiet 12×6" 12×6"
10" Round 0.545 384 384 434 703 FPM Trunk 12×8" 16×6"
12" Round 0.785 626 626 708 798 FPM Trunk 16×8" 16×8"
14" Round 1.069 948 948 1,071 887 FPM Trunk 14×12" 22×8"
16" Round 1.396 1,357 1,357 1,526 972 FPM Noisy 16×14" 24×10"
18" Round 1.767 1,850 1,850 2,086 1047 FPM Noisy 20×14" 30×10"
20" Round 2.182 2,446 2,446 2,757 1121 FPM Noisy 22×16" 30×12"
22" Round 2.640 3,148 3,148 3,548 1193 FPM Noisy 26×16" 30×14"
24" Round 3.142 3,963 3,963 4,465 1262 FPM Critical 28×18" 38×14"

How Every Row on This Equal-Friction Chart Is Calculated

1. Maximum CFM Solver per Diameter

For each nominal round diameter d (4" through 24"), the chart solves the ASHRAE 2025 Chapter 21 Darcy-Weisbach / Altshul-Tsal friction equation for the exact volumetric flow rate whose straight-run pressure drop equals the chosen friction rate:

ΔP₁₀₀(CFM, d, ε) = f × (1200 / d) × (V / 4005)² = FR_target
V = CFM / (π × (d / 12)² / 4)

Wall roughness factors follow ASHRAE Ch. 21 Table 1: Galvanized Steel ε = 0.0003 ft (medium-smooth), Fully Extended Flexible Wire-Helix Duct ε = 0.003 ft (Example 6 design value; Table 1 range 0.0003–0.003 ft), and Preformed Rigid Fibrous Duct Board using the site’s medium-rough group representative value ε = 0.003 ft (ASHRAE Table 1 provisionally assigns rigid fiberglass duct to medium-rough without a single measured ε).

2. Velocity Cap & Rectangular Equivalents

Each row displays the airflow velocity at maximum friction-rated capacity along with two even-inch Huebscher rectangular sheet-metal equivalents strictly satisfying dₑ ≥ d near 1.5:1 (compact joist bay) and 2.5:1 (shallow trunk):

dₑ = 1.30 × (W × H)^0.625 / (W + H)^0.25 ≥ d
Acoustic Bands: Quiet < 700 · Trunk 700–900 · Noisy > 900 FPM

Need custom friction rates (0.03–0.25 in. wg), up to 4:1 aspect ratios, or a full multi-room jobsite takeoff? Open the DuctCFM HVAC Duct Size Calculator & Digital Duct Wheel.

Chart Assumptions & Field Limits

  • Velocity Cap Overrides Friction on Large Trunks: Notice that 16"–24" metal ducts at 0.08–0.10 in. wg exceed 900 FPM. Per ACCA Manual D residential noise limits, drop main supply trunks to 0.06 in. wg or upsize until velocity stays at or below 900 FPM (and below 700 FPM in bedroom branches).
  • Worked Lookup Walkthrough (97 CFM & 300 CFM @ 0.08 in. wg): Enter 97 CFM in galvanized sheet metal to see exact unrounded matching in action: a 6" round duct maxes out at 96.93 CFM (rounded to 97 in compact tables), so strict compliance advances to 7" Round (147 CFM max, 549 FPM quiet, 8×6" or 12×4" rect). Entering 300 CFM in galvanized sheet metal highlights 10" Round (384 CFM max, 703 FPM trunk, 12×8" or 16×6" rect), matching our CFM & ACH Calculator. Switch material to Flex Duct at 300 CFM and capacity drops so the same 10" run remains compliant at 331 CFM max (330.52 CFM exact), while 8" branches drop from 210 CFM (metal) to 183 CFM (extended flex).
  • Choosing Between 0.06, 0.08, 0.10, and 0.12 in. wg: Long residential attic trunks with 300–500 ft of Total Effective Length (TEL) and 0.25 in. wg of Available Static Pressure typically fall near 0.05–0.07 in. wg/100 ft. Compact basement systems with short metal trunks can operate at 0.08–0.10 in. wg/100 ft, while 0.12 in. wg is reserved for short high-static commercial or garage runs where elevated duct velocity is acceptable.
  • Straight-Run Equivalent Length Only: Chart capacities represent 100 ft of straight, taut ductwork at standard sea-level air (0.075 lb/ft³). Account for elbow, takeoff, boot, and filter pressure drops before selecting a final friction rate.

Duct Sizing Chart FAQ

Why does a static 0.08 in. wg duct chart fail when switching to flex duct?

Most printed PDF charts assume smooth galvanized steel (ε = 0.0003 ft). Under ASHRAE 2025 Chapter 21 Table 1 & Example 6, fully extended wire-helix flex duct uses ε = 0.003 ft—so an 8-inch extended flex run carries roughly 183 CFM at 0.08 in. wg versus ~210 CFM for smooth galvanized steel, and field compression lowers capacity further. Toggle Material to Flex Duct above to recalculate every row automatically.

When should I switch from 0.08 to 0.10 in. wg on the duct sizing chart?

Use 0.10 in. wg only when your air handler has adequate Available Static Pressure (ASP) and short Total Effective Length (TEL), typically compact closet or garage installations. Long attic runs with multiple trunk transitions often require 0.06–0.07 in. wg to avoid starving far bedrooms.

Can I use the rectangular equivalent sizes directly for return air trunks?

Yes, Huebscher equivalent dimensions apply equally to supply and return trunks at the same friction rate. However, return trunks are commonly sized slightly more generously (0.06 in. wg or < 700 FPM) to minimize filter grille noise in hallways.

Why does target-CFM matching sometimes jump to the next nominal diameter by 1 CFM?

To stay strictly compliant with your target friction rate, the chart evaluates unrounded Darcy-Weisbach maximum capacity before displaying rounded whole-CFM labels. For example, a 6-inch galvanized duct maxes out at 96.93 CFM at 0.08 in. wg, so entering 97 CFM highlights a 7-inch duct rather than silently exceeding 0.08 in. wg.